Roof DC isolation

Solar PV audit checklist items

Question and ratingRelevant standards and references

R-DCI 2
Is there evidence of any pre-existing roof damage?

Please note: Any damage identified may not be attributable to installer.

Applicable rating: No rating is applied

Not applicable

R-DCI 3
Is there evidence of loose connections in the DC cables and connection with signs of heat?

Applicable rating: Unsafe

AS/NZS 3000:2018 Clause 3.7.2.3

AS/NZS 5033:2021 Clause 3.4

R-DCI 27
Is there evidence of loose connections in the DC cables and connections with no signs of heat?

Applicable rating: Needs rectification

AS/NZS 3000:2018 Clause 3.7.2.3

AS/NZS 5033:2021 Clause 3.4

R-DCI 5
Are the DC isolator(s) at the array readily available and do they facilitate safe operation, inspection, testing and maintenance?

Applicable rating: Needs rectification

AS/NZS 3000:2018 Cl 1.4.19, 1.6.1(d) and 2.3.2.2.1

AS/NZS 5033:2021 Clause 4.3.5.3.1 (b)

R-DCI 6
If an array load break isolator has been installed, is it located adjacent to the array it controls?

Applicable rating: Improvements identified (For information)

AS/NZS 5033:2021 Clause 4.3.3.1

R-DCI 8
Confirm all components have not been issued with a recall notice from manufacturers or regulators?

Applicable rating: Needs rectification

Clean Energy Council and ACCC recall lists

R-DCI 9
Are installed d.c. isolator(s) on the Electrical Regulator Authorities Council (ERAC) list?

Applicable rating: Needs rectification

Refer to Energy Safe Victoria and ERAC lists

R-DCI 12
Do all array dc isolators conform to these requirements:

  • are rated for DC use?
  • conform with switch disconnector requirements of AS 60947.3 with utilization category d.c.-PV2?
  • interrupt all live conductors simultaneously?
  • are capable of being secured in the open position?
  • have an independent manual operation?
  • are not polarity sensitive?

Applicable rating: Needs rectification

AS/NZS 5033:2021 Clause 4.3.4.2.2

R-DCI 14
Is the DC isolator at the array(s) correctly wired?

Applicable rating: Needs rectification

AS/NZS 5033:2021 Clause 4.4.3.3

AS/NZS 3000:2018 Clause 4.1.2

R-DCI 15
Is the load breaking DC isolator located adjacent to the array(s) correctly rated for the required d.c. voltage and current?

Applicable rating: Unsafe

AS/NZS 5033:2021 Clause 4.3.4.2.3

R-DCI 28
Do all array load break disconnection devices conform to these requirements:

  • are readily available?
  • are installed external to the building?
  • are contained in metal enclosures of at least 0.2mm thickness OR are mounted on a non-combustible surface that extends at least 200mm beyond the sides of the disconnector OR are mounted on non-combustible shrouds that are made of metal surface at least 0.2mm thickness?
  • have any penetrations through a surface that protects against the spread of fire, with internal diameter greater than 5mm, sealed with a fire-retardant material?

Applicable rating: Needs rectification

AS/NZS 5033:2021 Clause 4.3.5.3.1

R-DCI 16
Does the DC enclosure(s) at the array have the required IP rating (minimum IP55 if installed outside)?

Applicable rating: Improvements identified (For information)

AS/NZS 5033:2021 Clause 4.4.6.1

R-DCI 29
Are all dedicated individual enclosures containing switch disconnection devices protected against the effects of weather and water as per appendix K of AS/NZS 5033:2021?

Applicable rating: Needs rectification

AS/NZS 5033:2021 clause 4.4.7.3

R-DCI 30
Have all array enclosures containing DC conductor terminations been installed in line with these conditions:

  • enclosure has been mounted onto its mounting bracket or wall using the screw locations and screw types specified by the manufacturer?
  • enclosures do not have debris or dust from installation process left inside once mounted?
  • all return conductors routed through an enclosure containing terminations maintain double insulation?

Applicable rating: Needs rectification

AS/NZS 5033:2021 clause 4.4.7.1

R-DCI 31
Do all array entry/exits into enclosures containing DC conductor terminations conform to these requirements:

  • conduit entry/exits and fittings are installed in accordance with manufacturer's instructions, including water ingress requirements such as being glued?
  • only manufacturer provided entry/exit points have been used?
  • cable glands, conduits and fitting do not enter/exit the top face of the enclosure (excluding entry/exit points between disconnection device/s, and PCE/s mounted indoors)?
  • silicone or sealant products are not used for sealing entry/exit points unless specified by the disconnector manufacturer's instructions?

Applicable rating: Needs rectification

AS/NZS 5033:2021 Clause 4.4.7.2.1

R-DCI 32
Do all array cable glands connected to DC enclosures containing d.c. conductor terminations and used in an outdoor environment conform to these requirements:

  • are used to enter/exit enclosures containing conductor terminations?
  • are installed so each cable enters/exits through an individual hole?
  • are rated to at least IP 56?
  • have a hole diameter to maintain IP rating for the cables used?
  • have any spare holes sealed with gland manufacturer's approved sealing plug?

Applicable rating: Needs rectification

AS/NZS 5033:2021 Clause 4.4.7.2.2

R-DCI 33
Where array cable glands enter/exit the side face of an enclosure containing d.c. conductor termination and installed in an outdoor environment, has an appropriate drip loop been installed, and are all glands located within a protected zone of 30 degree as outlined in figure 4.8 and 4.9 of AS/NZS 5033:2021?

Applicable rating: Needs rectification

AS/NZS 5033:2021 Clause 4.4.7.2.2

R-DCI 34
For all continuous conduit systems that have a section installed in an outdoor environment, and that terminate into an enclosure containing a disconnection device, has a liquid draining device been installed at the lowest point of the conduit system that is rated to at least IP56?

Applicable rating: Needs rectification

AS/NZS 5033:2021 Clause 4.4.7.2.3

R-DCI 35
Is there evidence of water found in array DC enclosures containing conductor terminations?

Applicable rating: Needs rectification

AS/NZS3000:2018 Clauses 4.1.2 and 4.1.3

AS/NZS 5033:2021 Clause 4.4.6 and 4.4.7

R-DCI 18
Are there signs of water damage observed at array DC enclosures containing conductor terminations?

Applicable rating: Unsafe

AS/NZS3000:2018 Clauses 4.1.2 and 4.1.3

AS/NZS 5033:2021 Clause 4.4.6 and 4.4.7

R-DCI 36 ***UPDATED***
Does the installed system contain a String Inverter (DC Components) or a Micro-Inverter System (AC Components)

Applicable rating: Information only

Not applicable

R-DCI 37
Has a load break disconnection device been installed adjacent to the PV modules of the PV array?

Applicable rating: Improvements identified (For information)

Not applicable

R-DCI 19
Number of DC isolators installed at the PV array/s.

Applicable rating: No rating is applied

Not applicable

R-DCI 21
Isolator Manufacturer at the PV array/s.

Applicable rating: No rating is applied

Not applicable

R-DCI 22
Isolator Model No. at the PV array/s.

Applicable rating: No rating is applied

Not applicable

R-DCI 23
Voltage rating per leg (V).

Applicable rating: No rating is applied

Not applicable

R-DCI 24
Current rating per leg (I).

Applicable rating: No rating is applied

Not applicable

R-DCI 25
Number of modules in series.

Applicable rating: No rating is applied

Not applicable

R-DCI 26
Number of modules in parallel.

Applicable rating: No rating is applied

Not applicable

Updated