G-DCI 1 Are all components verified as not having been issued with a recall notice from manufacturers or regulators? Applicable rating: Needs rectification | CEC and ACCC recall lists |
G-DCI 2 Are installed DC isolator(s) on the Electrical Regulator Authorities Council (ERAC) list? Applicable rating: Needs rectification | Refer to Energy Safe Victoria and ERAC lists |
G-DCI 3 Is there evidence of loose connections in the DC cables and connections with signs of heat (sight, smell etc)? Applicable rating: Unsafe | AS/NZS 3000:2018 Clause 3.7.2.3 AS/NZS 5033:2021 Clause 3 |
G-DCI 27 Is there evidence of loose connections in the DC cables and connections with no signs of heat (sight, smell etc)? Applicable rating: Needs rectification | AS/NZS 3000:2018 Clause 3.7.2.3 AS/NZS 5033:2021 Clause 3 |
G-DCI 5 Is the DC isolator (or DC C/B) able to be secured in the open position? Applicable rating: Needs rectification | AS/NZS 5033:2021 Clause 4.3.4.2.2 (e) |
G-DCI 6b Do all PCE adjacent and physically separate load break disconnection devices conform to the following requirements: - are readily available?
- are adjacent to the PCE?
- are contained in metal enclosures of at least 0.2mm thickness OR are mounted on a non-combustible surface that extends at least 200mm beyond the sides of the disconnector OR are mounted on non-combustible shrouds that are made of metal surface at least 0.2mm thickness?
- have any penetrations through a surface that protects against the spread of fire, with internal diameter greater than 5mm, sealed with a fire-retardant material?
Applicable rating: Improvements identified (For Information) | AS/NZS 5033:2021 Clause 4.5.4.1 |
G-DCI 7 Have all load break disconnection devices been labelled with the following text? "PV ARRAY d.c. ISOLATOR". Applicable rating: Improvements Identified (For Information) | AS/NZS 5033:2021 Clause 5.5.1 and 5.5.2.1 |
G-DCI 8 Do all DC enclosure(s) at the inverter have the required IP rating (minimum IP55 if outdoors, minimum IP2X if indoors)? Applicable rating: Improvements identified (For information) | AS/NZS 5033:2021 Clause 4.4.6 |
G-DCI 30 Are all dedicated individual enclosures containing switch disconnection devices protected against the effects of weather and water as per appendix K of AS/NZS 5033:2021? Applicable rating: Needs rectification | AS/NZS 5033:2021 Clause 4.4.7.3 |
G-DCI 31 Have all enclosures containing d.c. conductor terminations been installed in line with the following conditions: - enclosure has been mounted onto its mounting bracket or wall using the screw locations and screw types specified by the manufacturer?
- enclosures do not have debris or dust from installation process left inside once mounted?
- all return conductors routed through an enclosure containing terminations maintain double insulation?
Applicable rating: Needs rectification | AS/NZS 5033:2021 Clause 4.4.7.1 |
G-DCI 32 Do all entry/exits into enclosures containing DC conductor terminations conform to the following requirements: - conduit entry/exits and fittings are installed in accordance with manufacturer's instructions, including water ingress requirements such as being glued?
- only manufacturer provided entry/exit points have been used?
- cable glands, conduits and fitting do not enter/exit the top face of the enclosure (excluding entry/exit points between disconnection device/s, and PCE/s mounted indoors)?
- silicone or sealant products are not used for sealing entry/exit points unless specified by the disconnector manufacturer's instructions?
Applicable rating: Needs rectification | AS/NZS 5033:2021 Clause 4.4.7.2.1 |
G-DCI 33 Do all cable glands connected to DC enclosures containing DC conductor termination and used in an outdoor environment conform to the following installation requirements: - are used to enter/exit enclosures containing conductor terminations?
- are installed so each cable enters/exits through an individual hole?
- are rated to at least IP 56?
- have a hole diameter to maintain IP rating for the cables used?
- have any spare holes sealed with gland manufacturer's approved sealing plug?
Applicable rating: Needs rectification | AS/NZS 5033:2021 Clause 4.4.7.2.2 |
G-DCI 34 Where cable glands enter/exit the side face of an enclosure containing d.c. conductor terminations and installed in an outdoor environment, has an appropriate drip loop been installed, and are all glands located within a protected zone of 30 degree as outlined in figure 4.8 and 4.9 of AS/NZS 5033:2021? Applicable rating: Needs rectification | AS/NZS 5033:2021 Clause 4.4.7.2.2 |
G-DCI 36 For all continuous conduit systems that have a section installed in an outdoor environment, and that terminate into an enclosure containing a disconnection device, have all conduit ends been sealed with a gland conforming to AS/NZS 5033:2021 Cl 4.4.7.2.2? Applicable rating: Needs rectification | AS/NZS 5033:2021 Clause 4.4.7.2.3 |
G-DCI 35 For all continuous conduit systems that have a section installed in an outdoor environment, and that terminate into an enclosure containing a disconnection device, has a liquid draining device been installed at the lowest point of the conduit system that is rated to at least IP56? Applicable rating: Needs rectification | AS/NZS 5033:2021 Clause 4.4.7.2.3 |
G-DCI 29 Is there evidence of water found in ground DC enclosures containing conductor terminations? Applicable rating: Needs rectification | AS/NZS3000:2018 Clauses 4.1.2 and 4.1.3 AS/NZS 5033:2021 Clause 4.4.6 and 4.4.7 |
G-DCI 10 Are there signs of water damage observed at ground DC enclosures containing conductor terminations? Applicable rating: Unsafe | AS/NZS3000:2018 Clauses 4.1.2 and 4.1.3 AS/NZS 5033:2021 Clause 4.4.6 and 4.4.7 |
G-DCI 11 Are the DC isolator(s) at the inverter readily available and do they facilitate safe operation, inspection, testing and maintenance? Applicable rating: Needs rectification | AS/NZS 3000:2018 Cl 1.4.19, 1.6.1(d) and 2.3.2.2.1 AS/NZS 5033:2021 Clause 4.3.5.3.1 (b) |
G-DCI 12 Do all ground DC isolators conform to these requirements: - are rated for DC use?
- conform with switch disconnector requirements of AS 60947.3 with utilization category d.c.-PV2?
- interrupt all live conductors simultaneously?
- are capable of being secured in the open position?
- have an independent manual operation?
- are not polarity sensitive?
Applicable rating: Needs rectification | AS/NZS 5033:2021 Clause 4.3.4.2.2 |
G-DCI 14 Is the DC isolator(s) at the inverter correctly wired? Applicable rating: Needs rectification | AS/NZS 5033:2021 Clause 4.4.3.3 AS/NZS 3000:2018 Clause 4.1.2 |
G-DCI 15 Is the load breaking DC isolator(s) located adjacent to the inverter correctly rated for the required DC voltage and current? Applicable rating: Unsafe | AS/NZS 5033:2021 Clause 4.3.4.2.3 |
G-DCI 16 If multiple DC isolators are installed at the inverter, are they grouped/ganged so that they operate simultaneously, or grouped/ganged in a common location? Applicable rating: Improvements identified (For information) | AS/NZS 5033:2021 Clause 4.5.4.2 |
G-DCI 17 If multiple DC isolators are installed at the inverter, is there a sign stating "WARNING: MULTIPLE d.c. SOURCES - TURN OFF ALL d.c. ISOLATORS TO ISOLATE EQUIPMENT". Applicable rating: Needs rectification | AS/NZS 5033:5.5.2.1 |
G-DCI 18 Number of DC isolators installed at the inverter. Applicable rating: No rating is applied | Not applicable |
G-DCI 20 Isolator Manufacturer at the inverter. Applicable rating: No rating is applied | Not applicable |
G-DCI 21 Isolator Model No. at the inverter. Applicable rating: No rating is applied | Not applicable |
G-DCI 22 Voltage rating per leg (V). Applicable rating: No rating is applied | Not applicable |
G-DCI 23 Current rating per leg (I). Applicable rating: No rating is applied | Not applicable |
G-DCI 24 Number of modules in. Applicable rating: No rating is applied | Not applicable |
G-DCI 25 Number of modules in parallel. Applicable rating: No rating is applied | Not applicable |